Thermal issues: ECS Parameters, Sensors and Telemetry Modules List
Last updated July, 2020
ECS Parameters
The Víctor M. Blanco 4-meter Telescope Environmental Control System has more than 80 parameters (Table 1) collected by more than 69 sets of sensors (Table 2) and 27 ethenet telemetry modules (Table 3). The telemetry system is located from Glycol Pumps to the very top of the Blanco dome.
Several sensors (or instruments) can be connected to one ethernet telemetry module, and one sensor can measure one or more parameters.
The parameters are air temperatures, surface temperatures, fluid temperatures, humidity, air pressure, oil pressure, glycol flow, voltages and more.
A Python script runs on the telemetry machine getting sensor data from the telemetry modules and sending to the MariaDB database server for ECS (Fig 1).
Fig 1: Database structure for ECS (includes telemetry and control)
The data is updated every minute on DB tables and it is displayed on web depending on the area of Blanco Telescope (Fig 2).
id | name | unit | sensor_id | module_id |
---|---|---|---|---|
1 | pm_north_temp | Celsius | 101 | 9103 |
2 | pm_south_temp | Celsius | 102 | 9103 |
3 | pm_east_temp | Celsius | 103 | 9103 |
4 | pm_west_temp | Celsius | 104 | 9103 |
5 | pm_air_surface_temp | Celsius | 105 | 9103 |
6 | pm_surface_north_temp | Celsius | 101 | 9103 |
7 | pm_surface_south_temp | Celsius | 102 | 9103 |
8 | pm_surface_east_temp | Celsius | 103 | 9103 |
9 | pm_surface_west_temp | Celsius | 104 | 9103 |
10 | chimney_air_temp | Celsius | 203 | 9103 |
11 | utruss_north_temp | Celsius | 301 | 9105 |
12 | utruss_south_temp | Celsius | 302 | 9105 |
13 | utruss_east_temp | Celsius | 303 | 9105 |
14 | utruss_west_temp | Celsius | 304 | 9105 |
15 | outside_air_temp | Celsius | 501 | 9110 |
16 | m1_cooling_glycol_temp | Celsius | 502 | 9110 |
17 | m1_cooling_out_air_temp | Celsius | 503 | 9110 |
18 | m1_cooling_cell_air_temp | Celsius | 504 | 9110 |
19 | dome_floor_temp | Celsius | 505 | 9110 |
20 | m1_cooling_glycol_flow | GPM | 507 | 9102 |
21 | low_dome_temp | Celsius | 401 | 9106 |
22 | dome_humidity | % | 401 | 9106 |
23 | low_dome_dewpoint | Celsius | 401 | 9106 |
24 | clean_room_temp | Celsius | 402 | 9107 |
25 | clean_room_humidity | % | 402 | 9107 |
26 | clean_room_dewpoint | Celsius | 402 | 9107 |
27 | coude_room_temp | Celsius | 403 | 9108 |
28 | coude_room_humidity | % | 403 | 9108 |
29 | coude_room_dewpoint | Celsius | 403 | 9108 |
30 | m1_cooling_mamac_fdbk | Volt | 506 | 9102 |
33 | high_dome_temp | Celsius | 510 | 9115 |
36 | supply_oil_to_pad_temp | Celsius | 702 | 9109 |
37 | return_oil_from_pad_temp | Celsius | 703 | 9109 |
38 | c_floor_temp | Celsius | 508 | 9110 |
39 | oil_cooling_glycol_supply_temp | Celsius | 704 | 9114 |
40 | oil_cooling_glycol_return_temp | Celsius | 705 | 9114 |
41 | oil_before_cooler_temp | Celsius | 706 | 9114 |
42 | oil_after_cooler_temp | Celsius | 707 | 9114 |
43 | oil_cooling_vptrans_fdbk | Volt | 708 | 9112 |
44 | oil_cooling_glycol_flow | Volt | 709 | 9112 |
45 | oil_cooling_glycol_after_cooler_temp | Celsius | 710 | 9114 |
46 | oil_pressure | PSIG | 711 | 9112 |
47 | m1_cooling_glycol_from_cooler_temp | Celsius | 509 | 9109 |
48 | ahu_east_glycol_supply_temp | Celsius | 801 | 9203 |
49 | ahu_east_glycol_return_temp | Celsius | 802 | 9203 |
50 | ahu_east_air_out_temp | Celsius | 803 | 9203 |
51 | ahu_west_glycol_supply_temp | Celsius | 804 | 9206 |
52 | ahu_west_glycol_return_temp | Celsius | 805 | 9206 |
53 | ahu_west_air_out_temp | Celsius | 806 | 9206 |
54 | fcs_from_chiller2_glycol_temp | Celsius | 901 | 9301 |
55 | bcs_from_chiller1_glycol_temp | Celsius | 902 | 9301 |
56 | fcs_to_chiller2_glycol_temp | Celsius | 903 | 9301 |
57 | bcs_to_chiller1_glycol_temp | Celsius | 904 | 9301 |
58 | fcs_to_chiller2_glycol_flow | GPM | 905 | 9302 |
59 | decam_top_cap_temp | Celsius | 305 | 9105 |
60 | bcs_to_chiller1_glycol_flow | GPM | 906 | 9302 |
61 | ahu_east_glycol_flow | GPM | 907 | 9202 |
62 | ahu_west_glycol_flow | GPM | 908 | 9205 |
63 | ahu_east_valve_vfdbk | volt | 909 | 9202 |
64 | ahu_west_valve_vfdbk | volt | 910 | 9205 |
65 | cfloor_coil_glycol_supply_temp | Celsius | 1011 | 9203 |
66 | cfloor_coil_glycol_return_temp | Celsius | 1012 | 9203 |
67 | mfloor_coil_glycol_supply_temp | Celsius | 1013 | 9401 |
68 | mfloor_coil_glycol_return_temp | Celsius | 1014 | 9401 |
69 | ahu_east_freq_fdbk | Hz | 911 | 9202 |
70 | ahu_west_freq_fdbk | Hz | 912 | 9205 |
71 | pm_bottom_north_temp | Celsius | 110 | 9116 |
72 | pm_bottom_west_temp | Celsius | 111 | 9116 |
73 | pm_bottom_east_temp | Celsius | 112 | 9116 |
74 | pm_bottom_south_temp | Celsius | 107 | 9104 |
75 | pm_air_south_temp | Celsius | 105 | 9103 |
76 | pm_air_north_temp | Celsius | 106 | 9104 |
77 | pm_air_east_temp | Celsius | 108 | 9104 |
78 | pm_air_west_temp | Celsius | 109 | 9104 |
79 | low_dome_east_temp | Celsius | 404 | 9109 |
80 | low_dome_west_temp | Celsius | 405 | 9109 |
81 | tel_low_struct_cover | Celsius | 211 | 9104 |
82 | central_ring_girder_east | Celsius | 212 | 9104 |
83 | central_ring_girder_north | Celsius | 213 | 9116 |
84 | central_ring_girder_west | Celsius | 214 | 9116 |
id | sensor_type | location | description |
---|---|---|---|
101 | Surface Temperature RTD | M1 coated surface North (Before 2018 shutdown: edge glued 5cm below surface) | RTD Omega SA2C-RTD-3-100-A-40 Flexible Molded sensor (Before 2018 Shutdown: Omega F2020-100-B-100) |
102 | Surface Temperature RTD | M1 coated surface South (Before 2018 Shutdown: on edge glued 5cm below surface) | RTD Omega SA2C-RTD-3-100-A-40 Flexible Molded sensor (Before '18 Shutdown:F2020-100-B-100 on 1x1"Al) |
103 | Surface Temperature RTD | M1 coated surface East (Before 2018 shutdown: at edge glued 5cm below surface) | RTD Omega SA2C-RTD-3-100-A-40 Flexible Molded sensor (Before '18 shutdown:F2020-100-B-100 on 1x1"Al) |
104 | Surface Temperature RTD | M1 coated surface West (Before 2018 Shutdown: on edge glued 5cm below surface) | RTD Omega SA2C-RTD-3-100-A-40 Flexible Molded sensor (F2020-100-B-100 on 1x1" Al block) |
105 | Air Temperature RTD | M1 Air South (Before 2018 Shutdown: it was glued to coating) | RTD Omega PR-11-2-100-1/8-6-E (Before 2018 Shutdown: 1PT100FR828 thin film in ceramic body) |
106 | Air Temperature RTD | M1 Air North (Before 2018 Shutdown:M1 surface glued on north) | RTD Omega PR-11-2-100-1/8-6-E (Before 2018 Shutdown: F2020-100-B-100) |
107 | Bottom Temperature RTD | M1 bottom substrate South (Before 2018 Shutdown: M1 surface glued on south) | RTD Omega SA2C-RTD-3-100-A-40 Flexible Molded sensor (Before 2018 Shutdown:F2020-100-B-100) |
108 | Air Temperature RTD | M1 Air East (Before 2018 Shutdown: glued on surface east) | RTD Omega PR-11-2-100-1/8-6-E (Before 2018 Shutdown:F2020-100-B-100) |
109 | Air Temperature RTD | M1 Air West (Before 2018 Shutdown: surface glued on west) | RTD Omega PR-11-2-100-1/8-6-E (Before 2018 Shutdown: Omega F2020-100-B-100) |
110 | Bottom Temperature RTD | M1 substrate bottom North (New since 2018 Shutdown) | RTD Omega SA2C-RTD-3-100-A-40 Flexible Molded sensor |
111 | Bottom Temperature RTD | M1 substrate bottom West (New since 2018 Shutdown) | RTD Omega SA2C-RTD-3-100-A-40 Flexible Molded sensor |
112 | Bottom Temperature RTD | M1 substrate bottom East (New since 2018 Shutdown) | RTD Omega SA2C-RTD-3-100-A-40 Flexible Molded sensor |
203 | temperature | Chimney ladder 1m above cell | RTD PT100 Omega 1PT100FR828 in a 1x1x6 cm3 aluminium cylinder |
211 | Surface RTD | Cover (close to Petalos) | RTD Omega SA2C-RTD-3-100-A-40 Flexible Molded sensor |
212 | Surface RTD | Mount structure East | RTD Omega SA2C-RTD-3-100-A-40 Flexible Molded sensor |
213 | Surface RTD | Mount structure North | RTD Omega SA2C-RTD-3-100-A-40 Flexible Molded sensor |
214 | Surface RTD | Mount structure West | RTD Omega SA2C-RTD-3-100-A-40 Flexible Molded sensor |
301 | temperature | Top ring north side | RTD PT100 Omega PRTF-10-2-100-1/4-6-E |
302 | temperature | Top ring south side | RTD PT100 Omega PRTF-10-2-100-1/4-6-E |
303 | temperature | Top ring east side | RTD PT100 Omega PRTF-10-2-100-1/4-6-E |
304 | temperature | Top ring west side | RTD PT100 Omega PRTF-10-2-100-1/4-6-E |
305 | temperature | Decam Top Cap | Omega SA2F-RTD-3-100-A-40 FLEXIBLE MOLDED RTD SENSOR |
401 | temperature/rh/dewpoint | Old console level close to west stairs | Omega iTHP-2 industrial probe |
402 | temperature/rh/dewpoint | Clean Room | Omega iTHP-2 industrial probe |
403 | temperature/rh/dewpoint | Coude Room wall | Omega iTHP-2 industrial probe |
404 | Air Temperature RTD | East Wall side of Cass-Cage | RTD PT100 Omega PRTF-10-2-100-1/4-6-E on Channel 3 |
405 | Air Temperature RTD | West Wall side of Cass-Cage | RTD PT100 Omega PRTF-10-2-100-1/4-6-E on Channel 4 |
501 | temperature | Outside dome north at M level in a shelter | RTD PT100 Omega PRTF-10-2-100-1/4-6-E |
502 | temperature | Mirror Cooling: cooler input glycol pipe | RTD PT100 |
503 | temperature | Mirror Cooling: air temperature just after cooler | RTD PT100 |
504 | temperature | Mirror Cooling: air input in M1 cell at Dec Axis | RTD PT100 Omega PR-10-2-100-1/4-6-E |
505 | Surface Temperature RTD | Mirror floor above glycol coil | RTD Omega SA2C-RTD-3-100-A-40 Flexible Molded sensor(Bef 2018 Shutdown: 1PT100FR828 in Al 8x8x2cm3) |
506 | voltage dc | Mirror Cooling: v/p transducer feedback terminals | Mamac EP-310; terminals 5(+) and 6(-) |
507 | voltage dc | Mirror Cooling: cooler input glycol pipe | Omega Paddle Wheel Flow Sensor FP-5300 connected to Flowmeter FPM-800 terminals 3 and 4 |
508 | Floor temperature | C Floor (Old Console) above glycol coil | RTD PT100 Omega 1PT100FR828 thin film in ceramic body mounted in Aluminium Block 8x8x2 cm3 |
509 | temperature | Mirror Cooling: cooler output glycol pipe | Omega SA1-RTD-B surface RTD PT100 class B |
510 | temperature | Dome platform close to crane | Omega zED wireless temperature End Device (zCDR coordinator) |
601 | wind speed/wind dir | Old console above 1m over roof | Vaisala WS425 ultrasonic wind sensor rs-232 |
701 | temperature | Glycol pipe at Oil cooling system on P floor | RTD PT100 |
702 | temperature | Oil supply NE radial hydrostatic pad | RTD PT100 |
703 | temperature | Oil return NE radial hydrostatic pad | RTD PT100 |
704 | temperature | Oil Cooling: Glycol supply pipe | RTD PT100 |
705 | temperature | Oil Cooling: before cooler glycol pipe | RTD PT100 |
706 | temperature | Oil Cooling: oil pipe before cooling | RTD PT100 |
707 | temperature | Oil Cooling: oil pipe after cooling | RTD PT100 |
708 | voltage dc | Oil Cooling: V/P Transducer feedback terminals | n/a |
709 | voltage dc | Oil Cooling: glycol input line before cooler | Omega Paddle Wheel Flow Sensor FP-5300 connected to Flowmeter FPM-800 (terminals 3 and 4) |
710 | temperature | Oil Cooling: after cooler glycol pipe | Omega SA2C-RTD-3-100-A-40 |
711 | oil pressure | Oil Cooling: high pressure pump output (front panel) | Omega PX359-2KGI across R=126.6 to convert 4.011-20.036 mA output. Convertion is made in E1242 |
801 | temperature | AHU East Glycol Supply | Omega RTD PT100 surface |
802 | temperature | AHU East Glycol Return | Omega RTD PT100 surface |
803 | temperature | AHU East Air Out | RTD PT100 Omega PRTF-10-2-100-1/4-6-E |
804 | temperature | AHU West Glycol Supply | Omega RTD PT100 surface |
805 | temperature | AHU West Glycol Return | Omega RTD PT100 surface |
806 | temperature | AHU West Air Out | RTD PT100 Omega PRTF-10-2-100-1/4-6-E |
901 | temperature | FCS to Chiller2 | Omega SA1-RTD-B Surface RTD |
902 | temperature | FCS from Chiller2 | Omega SA1-RTD-B SURFACE RTD |
903 | temperature | BCS to Chiller1 | Omega SA1-RTD-B SURFACE RTD |
904 | temperature | BCS from Chiller1 | Omega SA1-RTD-B SURFACE RTD |
905 | voltage dc | FCS to Chiller2 | Onicon F-1200 Dual Turbine Flow meter with D-1201 Display Module |
906 | voltage dc | BCS to Chiller1 | Onicon F-1200 Dual Turbine Flow meter with D-1221 Display Module |
907 | voltage dc | AHU East Glycol Supply | Omega FP-5300 with Signal Cond. Omega iDRN-FP-FS in: 6-60Hz out:0-10v |
908 | voltage dc | AHU West Glycol Supply | Omega FP-5300 with Signal Cond. Omega iDRN-FP-FS in: 6-60Hz out:0-10v |
909 | voltage dc | AHU East Valve Feedback | Voltage feedback from Glycol 3way valve of AHU East |
910 | voltage dc | AHU West Valve Feedback | Voltage feedback from Glycol 3way valve of AHU West |
911 | voltage dc | AHU East Fan Freq Feedback | Voltage feedback from VFD converted to Hz |
912 | voltage dc | AHU West Fan Freq Feedback | Voltage feedback from VFD |
1011 | temperature | Glycol supply line to C Floor coil. MZ window at DECal Room | Omega Surface RTD PT100 |
1012 | temperature | Glycol return line from C Floor coil. MZ window at DECal room | Omega Surface RTD PT100 |
1013 | temperature | Glycol supply line to M Floor. P floor hatch | Omega Surface RTD PT100 |
1014 | temperature | Glycol return line to M Floor. P floor hatch | Omega Surface RTD PT100 |
module_name | module_location | description |
---|---|---|
E1241_m1cooling | MR floor | Moxa E1241 4ch AO |
E1242_m1cooling | MR floor | Moxa E1242 4ch AI/8ch DIO |
E1260_mirror_1 | Cass Cage | Moxa E1260 6ch RTD |
E1260_mirror_2 | Cass Cage | Moxa E1260 6ch RTD |
A6015_utruss | Upper Truss | ADAM 6015 7ch RTD |
iTHX_dome | Dome | Omega iTHX-W 1ch T-RH-DP |
iTHX_cleanroom | Clean Room | Omega iTHX-SD 1ch T-RH-DP. Not connected (UTB 139.229.13.142 00-03-34-00-cc-b1) |
iTHX_coude | Coude Room | Omega iTHX-W 1ch T-RH-DP |
E1260_OilCooling_1 | MR floor | Moxa E1260 6ch RTD |
E1260_m1cooling | MR floor | Moxa E1260 6ch RTD |
E1242_OilCooling | Oil pump room | Moxa E1242 4ch AI/8ch DIO |
E1241_OilCooling | Oil pump room | Moxa E1241 |
E1260_OilCooling_2 | Oil pump room | Moxa E1260 6ch RTD |
zCDR_dome | Dome | Omega zCDR wireless coordinator v2.4 |
E1260_mirror_3 | Cass Cage | Moxa E1260 6ch RTD |
E1241_AHU_East | Dome AHU East Old Console | Moxa E1241 4ch AO |
E1242_AHU_East | Dome AHU East Old Console | Moxa E1242 4ch AI/8ch DIO |
E1260_AHU_East | Dome AHU East Old Console | Moxa E1260 6ch RTD |
E1241_AHU_West | Dome AHU West M Floor | Moxa E1241 4ch AO |
E1242_AHU_West | Dome AHU West M Floor | Moxa E1242 4ch AI/8ch DIO |
E1260_AHU_West | Dome AHU West M Floor | Moxa E1260 6ch RTD |
E1260_Chillers | Glycol Pump Room | Moxa E1260 6ch RTD |
E1242_Chillers | Glycol Pump Room | Moxa E1242 4ch AI/8ch DIO |
E1260_FloorCooling | Oil pump room | Moxa E1260 6ch RTD |
E1242_FloorCooling | Oil pump room | Moxa E1242 4ch AI/8ch DIO |
E1241_FloorCooling | Oil pump room | Moxa E1241 4ch AO |